HORSEPOWER |
3 |
VOLTAGE |
230 |
PHASE |
1 |
MOTOR FULL LOAD CURRENT (NEC) AMPS | 17 | |
BRANCH CIRCUIT
PROTECTION |
INSTANTANEOUS TRIP CIRCUIT BREAKER GMCP/HMCP AMPS |
30 |
TIME DELAY (DUAL ELEMENT) FUSE - AMPS | 25 | |
CIRCUIT BREAKER TRIP RATING- AMPS | 40 | |
MINIMUM WIRE SIZE | COPPER (75ºC) THW,THHN,XHHW- FUSE (BREAKER) | 10/8 |
FUSIBLE SWITCH | HD SWITCH - NEMA 1 CATALOG # DH | 221NGB |
MAGNETIC STARTER
NEMA 1 ENCLOSURE |
STARTER ENCLOSURE NEMA 1 CATALOG # ECN08 | 11AAA |
NEMA SIZE | 1 | |
HEATER PACK CATALOG NUMBER - H | 2012B-3 |