Motor Circuit Chart

For NEMA type Starters

 

HORSEPOWER

3

VOLTAGE

460

PHASE

3

 

MOTOR FULL LOAD CURRENT (NEC) AMPS 4.8
BRANCH CIRCUIT

PROTECTION

INSTANTANEOUS TRIP CIRCUIT BREAKER GMCP/HMCP AMPS

7
TIME DELAY (DUAL ELEMENT) FUSE - AMPS 10
CIRCUIT BREAKER TRIP RATING- AMPS 15
MINIMUM WIRE SIZE COPPER (75ºC) THW,THHN,XHHW- FUSE (BREAKER) 14
FUSIBLE SWITCH HD SWITCH - NEMA 1      CATALOG # DH 361FGK
MAGNETIC STARTER

NEMA 1 ENCLOSURE

STARTER ENCLOSURE NEMA 1     CATALOG # ECN05 01AAA
NEMA SIZE 0
HEATER PACK CATALOG NUMBER -   H 2009B-3