HORSEPOWER |
75 |
|
VOLTAGE |
208 |
|
PHASE |
3 |
| MOTOR FULL LOAD CURRENT (NEC) AMPS | 221 | |
| BRANCH CIRCUIT
PROTECTION |
INSTANTANEOUS TRIP CIRCUIT BREAKER GMCP/HMCP AMPS |
400 |
| IME DELAY(DUAL ELEMENT)FUSE - AMPS | 300 | |
| CIRCUIT BREAKER TRIP RATING- AMPS | 300 | |
| MINIMUM WIRE SIZE | COPPER (75ºC) THW,THHN,XHHW- FUSE (BREAKER) | 300 |
| FUSIBLE SWITCH | HD SWITCH - NEMA 1 CATALOG # DH | 325FGK |
| MAGNETIC STARTER
NEMA 1 ENCLOSURE |
STARTER ENCLOSURE NEMA 1 CATALOG # ECN05 | 51AAA |
| NEMA SIZE | 5 | |
| HEATER PACK CATALOG NUMBER - H | 2008B-3 | |