Motor Circuit Chart

For NEMA type Starters

 

HORSEPOWER

75

VOLTAGE

208

PHASE

3

 

MOTOR FULL LOAD CURRENT (NEC) AMPS 221
BRANCH CIRCUIT

PROTECTION

INSTANTANEOUS TRIP CIRCUIT BREAKER GMCP/HMCP AMPS

400
IME DELAY(DUAL ELEMENT)FUSE - AMPS 300
CIRCUIT BREAKER TRIP RATING- AMPS 300
MINIMUM WIRE SIZE COPPER (75ºC) THW,THHN,XHHW- FUSE (BREAKER) 300
FUSIBLE SWITCH HD SWITCH - NEMA 1      CATALOG # DH 325FGK
MAGNETIC STARTER

NEMA 1 ENCLOSURE

STARTER ENCLOSURE NEMA 1     CATALOG # ECN05 51AAA
NEMA SIZE 5
HEATER PACK CATALOG NUMBER -   H 2008B-3